ABB / Two step residual overvoltage protection (ROV2PTOV) _ Setting & highlights _ AB2051

Table of Contents

Overview

The “Two step residual overvoltage protection (ROV2PTOV)” function calculates the residual voltage from the three-phase voltage input transformers or measures it from a single voltage input transformer fed from an open delta or neutral point voltage transformer.

For more detailed information on “Two step residual overvoltage protection (ROV2PTOV)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Two step residual overvoltage protection ROV2PTOV 2(U0>) 59N

Signals & Setting Parameters


ROV2PTOV function block

ROV2PTOV function block

ROV2PTOV Input signals

ROV2PTOV Input signals
Name Type Default Description
U3P GROUP SIGNAL Three phase voltages
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

ROV2PTOV Output signals

ROV2PTOV Output signals
Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2

ROV2PTOV Group settings (basic)

ROV2PTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationStep1 Off
On
On Enable execution of step 1
Characterist1 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time Selection of time delay curve type for step 1
U1> 1.0 – 200.0 %UB 0.1 30.0 Voltage setting/start val (DT & IDMT), step 1 in % of UBase
t1 0.00 – 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 – 60.000 s 0.001 5.000 Minimum operate time for inverse curves for step 1
k1 0.05 – 1.10 0.01 0.05 Time multiplier for the inverse time delay for step 1
HystAbs1 0.0 – 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off
On
On Enable execution of step 2
Characterist2 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time Selection of time delay curve type for step 2
U2> 1.0 – 100.0 %UB 0.1 45.0 Voltage setting/start val (DT & IDMT), step 2 in % of UBase
t2 0.000 – 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 – 60.000 s 0.001 5.000 Minimum operate time for inverse curves for step 2
k2 0.05 – 1.10 0.01 0.05 Time multiplier for the inverse time delay for step 2
HystAbs2 0.0 – 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

ROV2PTOV Group settings (advanced)

ROV2PTOV Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset1 0.000 – 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time curve step 1
ResetTypeCrv1 Instantaneous
Frozen timer
Linearly decreased
Instantaneous Selection of used IDMT reset curve type for step 1
tIReset1 0.000 – 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 – 200.000 0.001 1.000 Parameter A for customer programmable curve for step 1
BCrv1 0.50 – 100.00 0.01 1.00 Parameter B for customer programmable curve for step 1
CCrv1 0.0 – 1.0 0.1 0.0 Parameter C for customer programmable curve for step 1
DCrv1 0.000 – 60.000 0.001 0.000 Parameter D for customer programmable curve for step 1
PCrv1 0.000 – 3.000 0.001 1.000 Parameter P for customer programmable curve for step 1
CrvSat1 0 – 100 % 1 0 Tuning param for prog. over voltage IDMT curve, step 1
tReset2 0.000 – 60.000 s 0.001 0.025 Time delay in DT reset (s), step 2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly decreased
Instantaneous Selection of used IDMT reset curve type for step 2
tIReset2 0.000 – 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 – 200.000 0.001 1.000 Parameter A for customer programmable curve for step 2
BCrv2 0.50 – 100.00 0.01 1.00 Parameter B for customer programmable curve for step 2
CCrv2 0.0 – 1.0 0.1 0.0 Parameter C for customer programmable curve for step 2
DCrv2 0.000 – 60.000 0.001 0.000 Parameter D for customer programmable curve for step 2
PCrv2 0.000 – 3.000 0.001 1.000 Parameter P for customer programmable curve for step 2
CrvSat2 0 – 100 % 1 0 Tuning param for prog. over voltage IDMT curve, step 2

ROV2PTOV Non group settings (basic)

ROV2PTOV Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ROV2PTOV Monitored data

ROV2PTOV Monitored data
Name Type Values (Range) Unit Description
ULevel REAL kV Magnitude of measured voltage

Logics & highlights


Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Logic diagram for step 1, Definite time delay, DT operation

Logic diagram for step 1, Definite time delay, DT operation

Example for Definite Time Delay stage 1 reset

Example for Definite Time Delay stage 1 reset

Example for Definite Time Delay stage 1 operation

Example for Definite Time Delay stage 1 operation

Schematic design of Two step residual overvoltage protection ROV2PTOV