ABB / Two step undervoltage protection (UV2PTUV) _ Setting & highlights _ AB2049

Table of Contents

Overview

Undervoltages can occur in the power system during faults or abnormal conditions. The “Two step undervoltage protection (UV2PTUV)” function can be used to open circuit breakers to prepare for system restoration at power outages or as a long-time delayed back-up to the primary protection.

For more detailed information on “Two step undervoltage protection (UV2PTUV)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Two step undervoltage protection UV2PTUV 3U< 27

Signals & Setting Parameters


UV2PTUV function block

UV2PTUV function block

UV2PTUV Input signals

UV2PTUV Input signals
Name Type Default Description
U3P GROUP SIGNAL Three phase voltages
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

UV2PTUV Output signals

UV2PTUV Output signals
Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

UV2PTUV Group settings (basic)

UV2PTUV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationStep1 Off
On
On Enable execution of step 1
Characterist1 Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time Selection of time delay curve type for step 1
OpMode1 1 out of 3
2 out of 3
3 out of 3
1 out of 3 Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step 1
U1< 1.0 – 100.0 %UB 0.1 70.0 Voltage setting/start val (DT & IDMT) in % of UBase, step 1
t1 0.00 – 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 – 60.000 s 0.001 5.000 Minimum operate time for inverse curves for step 1
k1 0.05 – 1.10 0.01 0.05 Time multiplier for the inverse time delay for step 1
IntBlkSel1 Off
Block of trip
Block all
Off Internal (low level) blocking mode, step 1
IntBlkStVal1 1 – 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 1
tBlkUV1 0.000 – 60.000 s 0.001 0.000 Time delay of internal (low level) blocking for step 1
HystAbs1 0.0 – 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off
On
On Enable execution of step 2
Characterist2 Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time Selection of time delay curve type for step 2
OpMode2 1 out of 3
2 out of 3
3 out of 3
1 out of 3 Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step 2
U2< 1.0 – 100.0 %UB 0.1 50.0 Voltage setting/start val (DT & IDMT) in % of UBase, step 2
t2 0.000 – 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 – 60.000 s 0.001 5.000 Minimum operate time for inverse curves for step 2
k2 0.05 – 1.10 0.01 0.05 Time multiplier for the inverse time delay for step 2
IntBlkSel2 Off
Block of trip
Block all
Off Internal (low level) blocking mode, step 2
IntBlkStVal2 1 – 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 2
tBlkUV2 0.000 – 60.000 s 0.001 0.000 Time delay of internal (low level) blocking for step 2
HystAbs2 0.0 – 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

UV2PTUV Group settings (advanced)

UV2PTUV Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset1 0.000 – 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time curve step 1
ResetTypeCrv1 Instantaneous
Frozen timer
Linearly decreased
Instantaneous Selection of used IDMT reset curve type for step 1
tIReset1 0.000 – 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 – 200.000 0.001 1.000 Parameter A for customer programmable curve for step 1
BCrv1 0.50 – 100.00 0.01 1.00 Parameter B for customer programmable curve for step 1
CCrv1 0.0 – 1.0 0.1 0.0 Parameter C for customer programmable curve for step 1
DCrv1 0.000 – 60.000 0.001 0.000 Parameter D for customer programmable curve for step 1
PCrv1 0.000 – 3.000 0.001 1.000 Parameter P for customer programmable curve for step 1
CrvSat1 0 – 100 % 1 0 Tuning param for prog. under voltage IDMT curve, step 1
tReset2 0.000 – 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time curve step 2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly decreased
Instantaneous Selection of used IDMT reset curve type for step 2
tIReset2 0.000 – 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 – 200.000 0.001 1.000 Parameter A for customer programmable curve for step 2
BCrv2 0.50 – 100.00 0.01 1.00 Parameter B for customer programmable curve for step 2
CCrv2 0.0 – 1.0 0.1 0.0 Parameter C for customer programmable curve for step 2
DCrv2 0.000 – 60.000 0.001 0.000 Parameter D for customer programmable curve for step 2
PCrv2 0.000 – 3.000 0.001 1.000 Parameter P for customer programmable curve for step 2
CrvSat2 0 – 100 % 1 0 Tuning param for prog. under voltage IDMT curve, step 2

UV2PTUV Non group settings (basic)

UV2PTUV Non group settings (basic)
Name Values (Range) Unit Step Default Description
ConnType PhN DFT
PhPh RMS
PhN RMS
PhPh DFT
PhN DFT Group selector for connection type
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

UV2PTUV Monitored data

UV2PTUV Monitored data
Name Type Values (Range) Unit Description
UL1 REAL kV Voltage in phase L1
UL2 REAL kV Voltage in phase L2
UL3 REAL kV Voltage in phase L3

Logics & highlights


Voltage used for the inverse time characteristic integration

Voltage used for the inverse time characteristic integration

Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at different reset types

Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at different reset types

Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different reset types

Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different reset types

Logic diagram for step 1, DT operation

Logic diagram for step 1, DT operation

Example for Definite Time Delay stage1 reset

Example for Definite Time Delay stage1 reset

Example for Definite Time Delay stage1 operation

Example for Definite Time Delay stage1 operation

Blocking function

Blocking function

Schematic design of Two step undervoltage protection UV2PTUV

Schematic design of Two step undervoltage protection UV2PTUV