Overview
Conventional protection functions cannot detect the broken conductor condition. The “Broken conductor check (BRCPTOC)” function, consisting of continuous phase selective current unsymmetrical check on the line where the IED is connected, gives an alarm or trip at detecting broken conductors.
For more detailed information on “Broken conductor check (BRCPTOC)”, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Broken conductor check | BRCPTOC | – | 46 |
Signals & Setting Parameters
BRCPTOC function block
BRCPTOC Input signals
BRCPTOC Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Group signal for current input |
BLOCK | BOOLEAN | 0 | Block of function |
BLKTR | BOOLEAN | 0 | Block of trip |
BRCPTOC Output signals
BRCPTOC Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Operate signal of the protection logic | |
START | BOOLEAN | Start signal of the protection logic | |
BRCPTOC Group settings (basic)
BRCPTOC Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation Off / On |
Iub> | 50 – 90 | %IM | 1 | 50 | Highest and lowest phase currents difference in % of highest phase current |
IP> | 5 – 100 | %IB | 1 | 20 | Minimum phase current for operation of Iub> in % of IBase |
tOper | 0.000 – 60.000 | s | 0.001 | 5.000 | Operate time delay |
BRCPTOC Group settings (advanced)
BRCPTOC Group settings (advanced) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
tReset | 0.010 – 60.000 | s | 0.001 | 0.100 | Time delay in reset |
BRCPTOC Non group settings (basic)
BRCPTOC Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
BRCPTOC Monitored data
BRCPTOC Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
IUNBAL | REAL | – | – | Measured unbalance of phase currents |