ABB / Broken conductor check (BRCPTOC) _ Setting & highlights _ AB2046

Table of Contents

Overview

Conventional protection functions cannot detect the broken conductor condition. The “Broken conductor check (BRCPTOC)” function, consisting of continuous phase selective current unsymmetrical check on the line where the IED is connected, gives an alarm or trip at detecting broken conductors.

For more detailed information on “Broken conductor check (BRCPTOC)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Broken conductor check BRCPTOC 46

Signals & Setting Parameters


BRCPTOC function block

BRCPTOC function block

BRCPTOC Input signals

BRCPTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

BRCPTOC Output signals

BRCPTOC Output signals
Name Type Description
TRIP BOOLEAN Operate signal of the protection logic
START BOOLEAN Start signal of the protection logic

BRCPTOC Group settings (basic)

BRCPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
Iub> 50 – 90 %IM 1 50 Highest and lowest phase currents difference in % of highest phase current
IP> 5 – 100 %IB 1 20 Minimum phase current for operation of Iub> in % of IBase
tOper 0.000 – 60.000 s 0.001 5.000 Operate time delay

BRCPTOC Group settings (advanced)

BRCPTOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset 0.010 – 60.000 s 0.001 0.100 Time delay in reset

BRCPTOC Non group settings (basic)

BRCPTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

BRCPTOC Monitored data

BRCPTOC Monitored data
Name Type Values (Range) Unit Description
IUNBAL REAL Measured unbalance of phase currents

Logics & highlights


Simplified logic diagram for Broken conductor check BRCPTOC

Simplified logic diagram for Broken conductor check BRCPTOC