For more detailed information on “Directional overpower protection (GOPPDOP)” function , refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional overpower protection GOPPDOP   32

Signals & Setting Parameters


GOPPDOP function block

GOPPDOP function block

GOPPDOP Input signals

GOPPDOP Input signals
Name Type Default Description
I3P GROUP SIGNAL Current group connection
U3P GROUP SIGNAL Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

GOPPDOP Output signals

GOPPDOP Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active power P in MW
PPERCENT REAL Active power P in % of SBase
Q REAL Reactive power Q in MVAr
QPERCENT REAL Reactive power Q in % of SBase

GOPPDOP Group settings (basic)

GOPPDOP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OpMode1 Off
OverPower
OverPower Operation mode for stage 1 Off / On
Power1 0.0 – 500.0 %SB 0.1 120.0 Stage 1 overpower setting in Angle1 direction in % of SBase
Angle1 -180.0 – 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivity stage 1
TripDelay1 0.01 – 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 – 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off
OverPower
OverPower Operation mode for stage 2 Off / On
Power2 0.0 – 500.0 %SB 0.1 120.0 Stage 2 overpower setting in Angle2 direction in % of SBase
Angle2 -180.0 – 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivity stage 2
TripDelay2 0.01 – 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 – 6000.00 s 0.01 0.06 Drop-off delay for stage 2

GOPPDOP Group settings (advanced)

GOPPDOP Group settings (advanced)
Name Values (Range) Unit Step Default Description
k 0.000 – 0.999 0.001 0.000 Low pass filter coefficient for power measurement, P and Q
Hysteresis1 0.2 – 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % of SBase
Hysteresis2 0.2 – 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % of SBase
IAmpComp5 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 5% of Ir
IAmpComp30 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 30% of Ir
IAmpComp100 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 100% of Ir
UAmpComp5 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 5% of Ur
UAmpComp30 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 30% of Ur
UAmpComp100 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 100% of Ur
IAngComp5 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 5% of Ir
IAngComp30 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 30% of Ir
IAngComp100 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 100% of Ir

GOPPDOP Non group settings (basic)

GOPPDOP Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups
Mode L1, L2, L3
Arone
Pos Seq
L1L2 L2L3 L3L1
L1
L2
L3
Pos Seq Selection of measured current and voltage

GOPPDOP Monitored data

GOPPDOP Monitored data
Name Type Values
Name Type Values (Range) Unit Description
P REAL MW Active power P in MW
PPERCENT REAL % Active power P in % of SBase
Q REAL MVAr Reactive power Q in MVAr
QPERCENT REAL % Reactive power Q in % of SBase

Logics & highlights


Reverse power protection with underpower IED and overpower IED

Reverse power protection with underpower IED and overpower IED

Simplified logic diagram of the power protection function

Simplified logic diagram of the power protection function

Calibration curves

Calibration curves