ABB / Directional underpower protection (GUPPDUP) _ Setting & highlights _ AB2044

Table of Contents

Overview

For more detailed information on “Directional underpower protection (GUPPDUP)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional underpower protection GUPPDUP   37

Signals & Setting Parameters


GUPPDUP function block

GUPPDUP function block

GUPPDUP Input signals

GUPPDUP Input signals
Name Type Default Description
I3P GROUP SIGNAL Current group connection
U3P GROUP SIGNAL Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

GUPPDUP Output signals

GUPPDUP Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBase
Q REAL Reactive power in MVAr
QPERCENT REAL Reactive power in % of SBase

GUPPDUP Group settings (basic)

GUPPDUP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OpMode1 Off
UnderPower
UnderPower Operation mode for stage 1 Off / On
Power1 0.0 – 500.0 %SB 0.1 1.0 Stage 1 underpower setting in Angle1 direction in % of SBase
Angle1 -180.0 – 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivity stage 1
TripDelay1 0.01 – 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 – 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off
UnderPower
UnderPower Operation mode for stage 2 Off / On
Power2 0.0 – 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of SBase
Angle2 -180.0 – 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivity stage 2
TripDelay2 0.01 – 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 – 6000.00 s 0.01 0.06 Drop-off delay for stage 2

GUPPDUP Group settings (advanced)

GUPPDUP Group settings (advanced)
Name Values (Range) Unit Step Default Description
k 0.000 – 0.999 0.001 0.000 Low pass filter coefficient for power measurement, P and Q
Hysteresis1 0.2 – 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % SBase
Hysteresis2 0.2 – 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % SBase
IAmpComp5 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 5% of Ir
IAmpComp30 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 30% of Ir
IAmpComp100 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates current error at 100% of Ir
UAmpComp5 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 5% of Ur
UAmpComp30 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 30% of Ur
UAmpComp100 -10.000 – 10.000 % 0.001 0.000 Amplitude correction compensates voltage error at 100% of Ur
IAngComp5 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 5% of Ir
IAngComp30 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 30% of Ir
IAngComp100 -10.000 – 10.000 Deg 0.001 0.000 Corr of error betw current and voltage angles at 100% of Ir

GUPPDUP Non group settings (basic)

GUPPDUP Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups
Mode L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
Pos Seq Selection of measured current and voltage

GUPPDUP Monitored data

GUPPDUP Monitored data
Name Type Values (Range) Unit Description
P REAL MW Active Power in MW
PPERCENT REAL % Active power in % of SBase
Q REAL MVAr Reactive power in MVAr
QPERCENT REAL % Reactive power in % of SBase

Logics & highlights


Protection with underpower IED and overpower IED

Protection with underpower IED and overpower IED

Simplified logic diagram of the power protection function

Simplified logic diagram of the power protection function

Calibration curves

Calibration curves