Overview

An open phase can cause negative and zero sequence currents which cause thermal stress on rotating machines and can cause unwanted operation of zero sequence or negative sequence current functions. The “Pole discordance protection (CCPDSC)” function operates based on information from auxiliary contacts of the circuit breaker for the three phases with additional criteria from unsymmetrical phase currents when required.

For more detailed information on “Pole discordance protection (CCPDSC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pole discordance protection CCPDSC PD 52PD

Signals & Setting Parameters


CCPDSC function block

CCPDSC function block

CCPDSC Input signals

CCPDSC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase currents
BLOCK BOOLEAN 0 Block of function
BLKDBYAR BOOLEAN 0 Block of function at CB single phase auto re-closing cycle
CLOSECMD BOOLEAN 0 Close order to CB
OPENCMD BOOLEAN 0 Open order to CB
EXTPDIND BOOLEAN 0 Pole discordance signal from CB logic
POLE1OPN BOOLEAN 1 Pole one opened indication from CB
POLE1CL BOOLEAN 0 Pole one closed indication from CB
POLE2OPN BOOLEAN 1 Pole two opened indication from CB
POLE2CL BOOLEAN 0 Pole two closed indication from CB
POLE3OPN BOOLEAN 1 Pole three opened indication from CB
POLE3CL BOOLEAN 0 Pole three closed indication from CB

CCPDSC Output signals

CCPDSC Output signals
Name Type Description
TRIP BOOLEAN Trip signal to CB
START BOOLEAN Trip condition TRUE, waiting for time delay

CCPDSC Group settings (basic)

CCPDSC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
tTrip 0.000 – 60.000 s 0.001 0.300 Time delay between trip condition and trip signal
ContSel Off
PD signal from CB
Pole pos aux cont.
Off Contact function selection
CurrSel Off
CB oper monitor
Continuous monitor
Off Current function selection
CurrUnsymLevel 0 – 100 % 1 80 Unsym magn of lowest phase current compared to the highest.
CurrRelLevel 0 – 100 %IB 1 10 Current magnitude for release of the function in % of IBase

CCPDSC Non group settings (basic)

CCPDSC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

CCPDSC Monitored data

CCPDSC Monitored data
Name Type Values (Range) Unit Description
IMin REAL A Lowest phase current
IMax REAL A Highest phase current

Logics & highlights


Pole discordance external detection logic

Pole discordance external detection logic

Pole discordance signals for internal logic

Pole discordance signals for internal logic

Simplified block diagram of pole discordance function CCPDSC – contact and current based

Simplified block diagram of pole discordance function CCPDSC - contact and current based