ABB / Stub protection (STBPTOC) _ Setting & highlights _ AB2042

Table of Contents

Overview

When a power line is taken out of service for maintenance and the line disconnector is opened in multi-breaker arrangements the voltage transformers will mostly be outside on the disconnected part. The primary line distance protection will thus not be able to operate and must be blocked. The “Stub protection (STBPTOC)” function covers the zone between the current transformers and the open disconnector. The three-phase instantaneous overcurrent function is released from a normally open, NO (b) auxiliary contact on the line disconnector.

For more detailed information on “Stub protection (STBPTOC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Stub protection STBPTOC 3I>STUB 50STB

Signals & Setting Parameters


STBPTOC function block

STBPTOC function block

STBPTOC Input signals

STBPTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase currents
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
RELEASE BOOLEAN 0 Release of stub protection

STBPTOC Output signals

STBPTOC Output signals
Name Type Description
TRIP BOOLEAN General trip
START BOOLEAN General start

STBPTOC Group settings (basic)

STBPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
ReleaseMode Release
Continuous
Release Release of stub protection
I> 5 – 2500 %IB 1 200 Operate current level in % of IBase

STBPTOC Group settings (advanced)

STBPTOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
tDelay 0.000 – 60.000 s 0.001 0.000 Time delay

STBPTOC Non group settings (basic)

STBPTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

STBPTOC Monitored data

STBPTOC Monitored data
Name Type Values (Range) Unit Description
IL1 REAL A Current in phase L1
IL2 REAL A Current in phase L2
IL3 REAL A Current in phase L3

Logics & highlights


Simplified logic diagram for Stub protection

Simplified logic diagram for Stub protection