ABB / Breaker failure protection (CCRBRF) _ Setting & highlights _ AB2041

Table of Contents

Overview

The “Breaker failure protection (CCRBRF)” function ensures a fast backup tripping of the surrounding breakers in case the own breaker fails to open. CCRBRF measurement criterion can be current based, CB position based or an adaptive combination of these two conditions.

For more detailed information on “Breaker failure protection (CCRBRF)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker failure protection, 3-phase activation and output CCRBRF 3I>BF 50BF

Signals & Setting Parameters


CCRBRF function block

CCRBRF function block

CCRBRF Input signals

CCRBRF Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase group signal for current inputs
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start for breaker failure protection function
STL1 BOOLEAN 0 Start signal for phase L1
STL2 BOOLEAN 0 Start signal for phase L2
STL3 BOOLEAN 0 Start signal for phase L3
CBCLDL1 BOOLEAN 0 Circuit breaker closed in phase L1
CBCLDL2 BOOLEAN 0 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 0 Circuit breaker closed in phase L3
CBFLT BOOLEAN 0 CB faulty, unable to trip. Backup trip instantaneously

CCRBRF Output signals

CCRBRF Output signals
Name Type Description
TRBU BOOLEAN Backup trip by breaker failure protection function
TRBU2 BOOLEAN Second backup trip by breaker failure protection function
TRRET BOOLEAN Retrip by breaker failure protection function
TRRETL1 BOOLEAN Retrip by breaker failure protection function phase L1
TRRETL2 BOOLEAN Retrip by breaker failure protection function phase L2
TRRETL3 BOOLEAN Retrip by breaker failure protection function phase L3
CBALARM BOOLEAN Alarm for faulty circuit breaker
STALARM BOOLEAN External start signal timed out, when by setting StartMode the external start signal is followed (i.e. when is NOT Latched)

CCRBRF Non group settings (basic)

CCRBRF Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

CCRBRF Group settings (basic)

CCRBRF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
FunctionMode Current
CB Pos
Current or CB Pos
Current Selection of measurement principle: Current / CB Position / Current or CB Position
StartMode LatchedStart
FollowStart
FollowStart&Mode
LatchedStart Select how t1 and t2 timers are run: By external start signals which is internally latched / Follow the external start signal only / Follow external start signal and selected FunctionMode
tStartTimeout 0.5 – 600.0 s 0.1 1.0 Time delay after which the external start signal will be ignored, when by setting StartMode the external start signal is followed (i.e. when is NOT Latched)
BuTripMode 2 out of 4
1 out of 3
1 out of 4
1 out of 3 Select backup trip mode when t2 timer expires and current measurement is used: 2 elements operate out of three phases and neutral / 1 element operates out of three phases / 1 element operates out of three phases and neutral
RetripMode Off
UseFunctionMode
Always
Off Select retrip mode when t1 timer expires: Off / use FunctionMode to check / always without any check
IPh> 5 – 200 %IB 1 10 Operate phase current level in % of IBase
IN> 2 – 200 %IB 1 10 Operate residual current level in % of IBase
t1 0.000 – 60.000 s 0.001 0.000 Time delay of retrip
t2 0.000 – 60.000 s 0.001 0.150 Time delay of backup trip
t2MPh 0.000 – 60.000 s 0.001 0.150 Time delay of backup trip at multi- phase start. It can be used to speed up backup trip command for multi- phase faults on OHLs
tPulse 0.010 – 60.000 s 0.001 0.200 Minimum trip pulse duration

CCRBRF Group settings (advanced)

CCRBRF Group settings (advanced)
Name Values (Range) Unit Step Default Description
I>BlkCBPos 5 – 200 %IB 1 20 I> in % of IBase to block operation based on CB Position when FunctionMode=Current or CB Pos
t3 0.000 – 60.000 s 0.001 0.030 Additional time delay which is added to t2. It can be used as a second backup trip
tCBAlarm 0.000 – 60.000 s 0.001 5.000 Time delay for alarm when faulty circuit breaker indicated

CCRBRF Monitored data

CCRBRF Monitored data
Name Type Values (Range) Unit Description
IL1 REAL A Measured current in phase L1
IL2 REAL A Measured current in phase L2
IL3 REAL A Measured current in phase L3
IN REAL A Measured residual current

Logics & highlights


Simplified overall logic for LatchedStart

Simplified overall logic for LatchedStart

Simplified overall logic for FollowStart

Simplified overall logic for FollowStart

Simplified overall logic for FollowStart&Mode

Simplified overall logic for FollowStart&Mode

Start logic for all three Function Modes of operation

Start logic for all three Function Modes of operation

Reset logic in latched mode

Reset logic in latched mode

Simplified retrip logic

Simplified retrip logic

Simplified backup trip logic

Simplified backup trip logic