Overview
The increasing utilization of the power system closer to the thermal limits has generated a need of a thermal overload protection for power lines. A thermal overload will often not be detected by other protection functions and the introduction of the thermal overload protection can allow the protected circuit to operate closer to the thermal limits.
For more detailed information on “Thermal overload protection, one time constant, Celsius/Fahrenheit (LCPTTR/LFPTTR)” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Thermal overload protection, one time constant, Celsius | LCPTTR | 26 | |
Thermal overload protection, one time constant, Fahrenheit | LFPTTR | 26 | |
Signals & Setting Parameters
LCPTTR function block
LCPTTR Input signals
LCPTTR Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Group signal for current input |
BLOCK | BOOLEAN | 0 | Block of function |
BLKTR | BOOLEAN | 0 | Block of trip |
ENMULT | BOOLEAN | 0 | Current multiplyer used when THOL is for two or more lines |
AMBTEMP | REAL | 0 | Ambient temperature from external temperature sensor |
SENSFLT | BOOLEAN | 0 | Validity status of ambient temperature sensor |
RESET | BOOLEAN | 0 | Reset of internal thermal load counter |
LCPTTR Output signals
LCPTTR Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Trip | |
START | BOOLEAN | Start Signal | |
ALARM | BOOLEAN | Alarm signal | |
LOCKOUT | BOOLEAN | Lockout signal | |
LCPTTR Group settings (basic)
LCPTTR Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation Off / On |
TRef | 0 – 300 | Deg C | 1 | 90 | End temperature rise above ambient of the line when loaded with IRef |
IRef | 0 – 400 | %IB | 1 | 100 | The load current (in % of IBase) leading to TRef temperature |
IMult | 1 – 5 | – | 1 | 1 | Current multiplier when function is used for two or more lines |
Tau | 1 – 1000 | Min | 1 | 45 | Time constant of the line in minutes. |
AlarmTemp | 0 – 200 | Deg C | 1 | 80 | Temperature level for start (alarm) |
TripTemp | 0 – 300 | Deg C | 1 | 90 | Temperature level for trip |
ReclTemp | 0 – 300 | Deg C | 1 | 75 | Temperature for reset of lockout after trip |
tPulse | 0.05 – 0.30 | s | 0.01 | 0.10 | Operate pulse length. Minimum one execution cycle |
AmbiSens | Off On |
– | – | Off | External temperature sensor available |
DefaultAmbTemp | -50 – 100 | Deg C | 1 | 20 | Ambient temperature used when AmbiSens is set to Off. |
DefaultTemp | -50 – 300 | Deg C | 1 | 50 | Temperature raise above ambient temperature at startup |
LCPTTR Non group settings (basic)
LCPTTR Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
LCPTTR Monitored data
LCPTTR Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
TTRIP | INTEGER | – | – | Estimated time to trip (in min) |
TENRECL | REAL | – | – | Estimated time to reset of lockout (in min) |
TEMP | REAL | – | deg | Calculated temperature of the device |
TEMPAMB | REAL | – | deg | Ambient temperature used in the calculations |
TERMLOAD | REAL | – | – | Temperature relative to operate temperature |
LFPTTR function block
LFPTTR Input signals
LFPTTR Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Group signal for current input |
BLOCK | BOOLEAN | 0 | Block of function |
BLKTR | BOOLEAN | 0 | Block of trip |
ENMULT | BOOLEAN | 0 | Current multiplyer used when THOL is for two or more lines |
AMBTEMP | REAL | 0 | Ambient temperature from external temperature sensor |
SENSFLT | BOOLEAN | 0 | Validity status of ambient temperature sensor |
RESET | BOOLEAN | 0 | Reset of internal thermal load counter |
LFPTTR Output signals
LFPTTR Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Trip | |
START | BOOLEAN | Start Signal | |
ALARM | BOOLEAN | Alarm signal | |
LOCKOUT | BOOLEAN | Lockout signal | |
LFPTTR Group settings (basic)
LFPTTR Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation Off / On |
TRef | 0 – 600 | Deg F | 1 | 160 | End temperature rise above ambient of the line when loaded with IRef |
IRef | 0 – 400 | %IB | 1 | 100 | The load current (in % of IBase) leading to TRef temperature |
IMult | 1 – 5 | – | 1 | 1 | Current multiplier when function is used for two or more lines |
Tau | 1 – 1000 | Min | 1 | 45 | Time constant of the line in minutes. |
AlarmTemp | 0 – 400 | Deg F | 1 | 175 | Temperature level for start (alarm) |
TripTemp | 0 – 600 | Deg F | 1 | 195 | Temperature level for trip |
ReclTemp | 0 – 600 | Deg F | 1 | 170 | Temperature for reset of lockout after trip |
tPulse | 0.05 – 0.30 | s | 0.01 | 0.10 | Operate pulse length. Minimum one execution cycle |
AmbiSens | Off On |
– | – | Off | External temperature sensor available |
DefaultAmbTemp | -50 – 250 | Deg F | 1 | 60 | Ambient temperature used when AmbiSens is set to Off. |
DefaultTemp | -50 – 600 | Deg F | 1 | 100 | Temperature raise above ambient temperature at startup |
LFPTTR Non group settings (basic)
LFPTTR Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
LFPTTR Monitored data
LFPTTR Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
TTRIP | INTEGER | – | – | Estimated time to trip (in min) |
TENRECL | REAL | – | – | Estimated time to reset of lockout (in min) |
TEMP | REAL | – | Temperatur e Fahrenheit | Calculated temperature of the device |
TEMPAMB | REAL | – | Temperatur e Fahrenheit | Ambient temperature used in the calculations |
TERMLOAD | REAL | – | – | Temperature relative to operate temperature |