ABB / Thermal overload protection, one time constant, Celsius/Fahrenheit (LCPTTR/LFPTTR) _ Setting & highlights _ AB2040

Table of Contents

Overview

The increasing utilization of the power system closer to the thermal limits has generated a need of a thermal overload protection for power lines. A thermal overload will often not be detected by other protection functions and the introduction of the thermal overload protection can allow the protected circuit to operate closer to the thermal limits.

For more detailed information on “Thermal overload protection, one time constant, Celsius/Fahrenheit (LCPTTR/LFPTTR)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Thermal overload protection, one time constant, Celsius LCPTTR   26
Thermal overload protection, one time constant, Fahrenheit LFPTTR   26

Signals & Setting Parameters


LCPTTR function block

LCPTTR function block

LCPTTR Input signals

LCPTTR Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

LCPTTR Output signals

LCPTTR Output signals
Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

LCPTTR Group settings (basic)

LCPTTR Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
TRef 0 – 300 Deg C 1 90 End temperature rise above ambient of the line when loaded with IRef
IRef 0 – 400 %IB 1 100 The load current (in % of IBase) leading to TRef temperature
IMult 1 – 5 1 1 Current multiplier when function is used for two or more lines
Tau 1 – 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 – 200 Deg C 1 80 Temperature level for start (alarm)
TripTemp 0 – 300 Deg C 1 90 Temperature level for trip
ReclTemp 0 – 300 Deg C 1 75 Temperature for reset of lockout after trip
tPulse 0.05 – 0.30 s 0.01 0.10 Operate pulse length. Minimum one execution cycle
AmbiSens Off
On
Off External temperature sensor available
DefaultAmbTemp -50 – 100 Deg C 1 20 Ambient temperature used when AmbiSens is set to Off.
DefaultTemp -50 – 300 Deg C 1 50 Temperature raise above ambient temperature at startup

LCPTTR Non group settings (basic)

LCPTTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

LCPTTR Monitored data

LCPTTR Monitored data
Name Type Values (Range) Unit Description
TTRIP INTEGER Estimated time to trip (in min)
TENRECL REAL Estimated time to reset of lockout (in min)
TEMP REAL deg Calculated temperature of the device
TEMPAMB REAL deg Ambient temperature used in the calculations
TERMLOAD REAL Temperature relative to operate temperature

LFPTTR function block

LFPTTR function block

LFPTTR Input signals

LFPTTR Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

LFPTTR Output signals

LFPTTR Output signals
Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

LFPTTR Group settings (basic)

LFPTTR Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
TRef 0 – 600 Deg F 1 160 End temperature rise above ambient of the line when loaded with IRef
IRef 0 – 400 %IB 1 100 The load current (in % of IBase) leading to TRef temperature
IMult 1 – 5 1 1 Current multiplier when function is used for two or more lines
Tau 1 – 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 – 400 Deg F 1 175 Temperature level for start (alarm)
TripTemp 0 – 600 Deg F 1 195 Temperature level for trip
ReclTemp 0 – 600 Deg F 1 170 Temperature for reset of lockout after trip
tPulse 0.05 – 0.30 s 0.01 0.10 Operate pulse length. Minimum one execution cycle
AmbiSens Off
On
Off External temperature sensor available
DefaultAmbTemp -50 – 250 Deg F 1 60 Ambient temperature used when AmbiSens is set to Off.
DefaultTemp -50 – 600 Deg F 1 100 Temperature raise above ambient temperature at startup

LFPTTR Non group settings (basic)

LFPTTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

LFPTTR Monitored data

LFPTTR Monitored data
Name Type Values (Range) Unit Description
TTRIP INTEGER Estimated time to trip (in min)
TENRECL REAL Estimated time to reset of lockout (in min)
TEMP REAL Temperatur e Fahrenheit Calculated temperature of the device
TEMPAMB REAL Temperatur e Fahrenheit Ambient temperature used in the calculations
TERMLOAD REAL Temperature relative to operate temperature

Logics & highlights


Functional overview of LCPTTR/LFPTTR

Functional overview of LCPTTR/LFPTTR