Overview

The “Four step directional negative phase sequence overcurrent protection (NS4PTOC)” function has an inverse or definite time delay independent for each step separately. All IEC and ANSI time delayed characteristics are available together with an optional user defined characteristic. The directional function is voltage polarized.

For more detailed information on “Four step directional negative phase sequence overcurrent protection (NS4PTOC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


NS4PTOC Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step negative sequence overcurrent protection NS4PTOC I2
4I–c–I
4I—–I
46I2

Signals & Setting Parameters


NS4PTOC function block

NS4PTOC function block

NS4PTOC Input signals

NS4PTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Group connection for operate current
I3PDIR GROUP SIGNAL Group connection for directional current
U3P GROUP SIGNAL Group connection for polarizing voltage
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

NS4PTOC Output signals

NS4PTOC Output signals
Name Type Description
TRIP BOOLEAN General trip signal
TR1 BOOLEAN Trip signal from step 1
TR2 BOOLEAN Trip signal from step 2
TR3 BOOLEAN Trip signal from step 3
TR4 BOOLEAN Trip signal from step 4
START BOOLEAN General start signal
ST1 BOOLEAN Start signal step 1
ST2 BOOLEAN Start signal step 2
ST3 BOOLEAN Start signal step 3
ST4 BOOLEAN Start signal step 4
STFW BOOLEAN Forward directional start signal
STRV BOOLEAN Reverse directional start signal

NS4PTOC Group settings (basic)

NS4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
EnDir Disable
Enable
Enable Enabling the Directional calculation
AngleRCA -180 – 180 Deg 1 65 Relay characteristic angle (RCA)
UPolMin 1 – 100 %UB 1 5 Minimum voltage level for polarization in % of UBase
I2>Dir 1 – 100 %IB 1 10 Residual current level in % of IBase for Direction release
DirMode1 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 1 (off, nodir, forward, reverse)
Characterist1 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 1
I2-1> 1 – 2500 %IB 1 100 Negative sequence current op level for step 1 in % of IBase
t1 0.000 – 60.000 s 0.001 0.000 Time delay of step 1 when definite time char. is selected
k1 0.05 – 999.00 0.01 0.05 Time multiplier for the step 1 selected time characteristic
IMin1 1.00 – 10000.00 %IB 1.00 100.00 Minimum current for step 1
t1Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 1
I1Mult 1.0 – 10.0 0.1 2.0 Multiplier for scaling the current setting value for step 1
DirMode2 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 2 (off, nodir, forward, reverse)
Characterist2 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv. IEC Very inv. IEC inv.
IEC Ext. inv. IEC S.T. inv. IEC L.T. inv.
IEC Def. Time Reserved Programmable RI type
RD type
ANSI Def. Time Time delay characteristic for step 2
I2-2> 1 – 2500 %IB 1 50 Negative sequence current op level for step 2 in % of IBase
t2 0.000 – 60.000 s 0.001 0.400 Time delay of step 2 when definite time char. is selected
k2 0.05 – 999.00 0.01 0.05 Time multiplier for the step 2 selected time characteristic
IMin2 1.00 – 10000.00 %IB 1.00 50 Minimum current for step 2
t2Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 2
I2Mult 1.0 – 10.0 0.1 2.0 Multiplier for scaling the current setting value for step 2
DirMode3 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 3 (off, nodir, forward, reverse)
Characterist3 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 3
I2-3> 1 – 2500 %IB 1 33 Negative sequence current op level for step 3 in % of IBase
t3 0.000 – 60.000 s 0.001 0.800 Time delay of step 3 when definite time char. is selected
k3 0.05 – 999.00 0.01 0.05 Time multiplier for the step 3 selected time characteristic
IMin3 1.00 – 10000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 3
I3Mult 1.0 – 10.0 0.1 2.0 Multiplier for scaling the current setting value for step 3
DirMode4 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 4 (off, nodir, forward, reverse)
Characterist4 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 4
I2-4> 1 – 2500 %IB 1 17 Negative sequence current op level for step 4 in % of IBase
t4 0.000 – 60.000 s 0.001 1.200 Time delay of step 4 when definite time char. is selected
k4 0.05 – 999.00 0.01 0.05 Time multiplier for the step 4 selected time characteristic
IMin4 1.00 – 10000.00 %IB 1.00 17 Minimum current for step 4
t4Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 4
I4Mult 1.0 – 10.0 0.1 2.0 Multiplier for scaling the current setting value for step 4

NS4PTOC Group settings (advanced)

NS4PTOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
ResetTypeCrv1 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step1 (Instantaneous / IEC / ANSI)
tReset1 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 1
tACrv1 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 1
tBCrv1 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 1
tCCrv1 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 1
tPRCrv1 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 1
tTRCrv1 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step
tCRCrv1 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 1
ResetTypeCrv2 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step2 (Instantaneous / IEC / ANSI)
tReset2 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 2
tACrv2 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 2
tBCrv2 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 2
tCCrv2 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 2
tPRCrv2 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 2
tTRCrv2 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 2
tCRCrv2 0.1 – 10.0 0.1 1.0 Param C for customized inverse reset time curve for step 2
ResetTypeCrv3 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step3 (Instantaneous / IEC / ANSI)
tReset3 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 3
tACrv3 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 3
tBCrv3 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 3
tCCrv3 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 3
tPRCrv3 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 3
tTRCrv3 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 3
tCRCrv3 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 3
ResetTypeCrv4 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step4 (Instantaneous / IEC / ANSI)
tReset4 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 4
tACrv4 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 4
tBCrv4 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 4
tCCrv4 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 4
tPRCrv4 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 4
tTRCrv4 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 4
tCRCrv4 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 4

NS4PTOC Non group settings (basic)

NS4PTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

NS4PTOC Monitored data

NS4PTOC Monitored data
Name Type Values (Range) Unit Description
IOp REAL A Operating current level
UPol REAL kV Polarizing voltage level
UPOLIANG REAL deg Polarizing angle between voltage and current

Logics & highlights


Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4

Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4

Operating characteristic for fault directional element

Operating characteristic for fault directional element

Simplified logic diagram for directional supervision element with integrated directional comparison step

Simplified logic diagram for directional supervision element with integrated directional comparison step