Table of Contents

ABB / Directional residual overcurrent protection four steps (EF4PTOC) _ Setting & highlights _ AB2037

Table of Contents

Overview

The “Directional residual overcurrent protection four steps (EF4PTOC)” function can be used as main protection for phase-to-earth faults. It can also be used to provide a system back-up, for example, in the case of the primary protection being out of service due to communication or voltage transformer circuit failure.

For more detailed information on “Directional residual overcurrent protection four steps (EF4PTOC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


EF4PTOC Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent protection, four steps EF4PTOC 4(3I>)
4I–c–I
4I—–I
51N_67N

Signals & Setting Parameters


EF4PTOC function block

EF4PTOC function block

EF4PTOC Input signals

EF4PTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Group connection for operate current
U3P GROUP SIGNAL Group connection for polarizing voltage
I3PPOL GROUP SIGNAL Group connection for polarizing current
I3PDIR GROUP SIGNAL Group connection for directional current
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command

EF4PTOC Output signals

EF4PTOC Output signals
Name Type Description
TRIP BOOLEAN General trip signal
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault function
STFW BOOLEAN Start signal forward direction
STRV BOOLEAN Start signal reverse direction
2NDHARMD BOOLEAN 2nd harmonic block signal

EF4PTOC Group settings (basic)

EF4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
EnDir Disable
Enable
Enable Enabling the Directional calculation
AngleRCA -180 – 180 Deg 1 65 Relay Characteristic Angle (RCA)
polMethod Voltage
Current
Dual
Voltage Type of polarization
UPolMin 1 – 100 %UB 1 1 Minimum voltage level for polarization in % of UBase
IPolMin 2 – 100 %IB 1 5 Minimum current level for polarization in % of IBase
RNPol 0.50 – 1000.00 Ohm 0.01 5.00 Real part of source impedance used for current polarisation
XNPol 0.50 – 3000.00 Ohm 0.01 40.00 Imaginary part of source imp. used for current polarisation
IN>Dir 1 – 100 %IB 1 10 Residual current level in % of IBase for Direction release
2ndHarmStab 5 – 100 % 1 20 Operate level of 2nd harmonic curr in
% of fundamental curr
BlkParTransf Off
On
Off Enable blocking at energizing of parallel transformers
UseStartValue IN1>
IN2>
IN3>
IN4>
IN4> Current level blk at parallel transf (step1, 2, 3 or 4)
SOTF Off
SOTF
UnderTime
SOTF&UnderTime
Off SOTF operation mode (Off/SOTF/ Undertime/SOTF&Undertime)
ActivationSOTF Open
Closed
CloseCommand
Open Select signal to activate SOTF: CB- Open/ -Closed/ -Close cmd
StepForSOTF Step 2
Step 3
Step 2 Select start from step 2 or 3 to start SOTF
HarmBlkSOTF Off
On
Off Enable harmonic restrain function in SOTF
tSOTF 0.000 – 60.000 s 0.001 0.200 Time delay for SOTF
t4U 0.000 – 60.000 s 0.001 1.000 Switch-onto-fault active time
ActUnderTime CB position
CB command
CB position Select signal to activate under time (CB Pos / CB Command)
tUnderTime 0.000 – 60.000 s 0.001 0.300 Time delay for under time
DirMode1 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 1 (Off, Non- dir, Forward, Reverse)
Characterist1 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 1
IN1> 1 – 2500 %IB 1 100 Residual current operate level for step 1 in % of IBase
t1 0.000 – 60.000 s 0.001 0.000 Def time delay or add time delay for inverse char of step 1
k1 0.05 – 999.00 0.01 0.05 Time multiplier for the step 1 selected time characteristic
IMin1 1.00 – 10000.00 %IB 1.00 100.00 Minimum operate residual current for step 1 in % of IBase
t1Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 1
IN1Mult 1.0 – 10.0 0.1 2.0 Multiplier for the residual current setting value for step 1
HarmBlock1 Off
On
On Enable block of step 1 from harmonic restrain
DirMode2 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 2 (Off, Non- dir, Forward, Reverse)
Characterist2 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 2
IN2> 1 – 2500 %IB 1 50 Residual current operate level for step 2 in % of IBase
t2 0.000 – 60.000 s 0.001 0.400 Def time delay or add time delay for inverse char of step 2
k2 0.05 – 999.00 0.01 0.05 Time multiplier for the step 2 selected time characteristic
IMin2 1.00 – 10000.00 %IB 1.00 50 Minimum operate residual current for step 2 in % of IBase
t2Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 2
IN2Mult 1.0 – 10.0 0.1 2.0 Multiplier for the residual current setting value for step 2
HarmBlock2 Off
On
On Enable block of step 2 from harmonic restrain
DirMode3 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 3 (Off, Non- dir, Forward, Reverse)
Characterist3 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 3
IN3> 1 – 2500 %IB 1 33 Residual current operate level for step 3 in % of IBase
t3 0.000 – 60.000 s 0.001 0.800 Def time delay or add time delay for inverse char of step 3
k3 0.05 – 999.00 0.01 0.05 Time multiplier for the step 3 selected time characteristic
IMin3 1.00 – 10000.00 %IB 1.00 33 Minimum operate residual current for step 3 in % of IBase
t3Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 3
IN3Mult 1.0 – 10.0 0.1 2.0 Multiplier for the residual current setting value for step 3
HarmBlock3 Off
On
On Enable block of step 3 from harmonic restrain
DirMode4 Off
Non-directional
Forward
Reverse
Non-directional Directional mode of step 4 (Off, Non- dir, Forward, Reverse)
Characterist4 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved Programmable
RI type
RD type
ANSI Def. Time Time delay characteristic for step 4
IN4> 1 – 2500 %IB 1 17 Residual current operate level for step 4 in % of IBase
t4 0.000 – 60.000 s 0.001 1.200 Def time delay or add time delay for inverse char of step 4
k4 0.05 – 999.00 0.01 0.05 Time multiplier for the step 4 selected time characteristic
IMin4 1.00 – 10000.00 %IB 1.00 17 Minimum operate residual current for step 4 in % of IBase
t4Min 0.000 – 60.000 s 0.001 0.000 Minimum operate time for inverse time characteristic step 4
IN4Mult 1.0 – 10.0 0.1 2.0 Multiplier for the residual current setting value for step 4
HarmBlock4 Off
On
On Enable block of step 4 from harmonic restrain

EF4PTOC Group settings (advanced)

EF4PTOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
IN1>Min 1 – 2500 %IB 1 1 Minimum used operate residual current level for step 1 in % of IBase, if IN1> is less than IN1>Min then IN1> is set to IN1>Min
IN1>Max 1 – 2500 %IB 1 2500 Maximum used operate residual current level for step 1 in % of IBase, if IN1> is greater than IN1>Max then IN1> is set to IN1>Max
ResetTypeCrv1 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step1 (Instantaneous / IEC / ANSI)
tReset1 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 1
tACrv1 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 1
tBCrv1 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 1
tCCrv1 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 1
tPRCrv1 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 1
tTRCrv1 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 1
tCRCrv1 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 1
IN2>Min 1 – 2500 %IB 1 1 Minimum used operate residual current level for step 2 in % of IBase, if IN2> is less than IN2>Min then IN2> is set to IN2>Min
IN2>Max 1 – 2500 %IB 1 2500 Maximum used operate residual current level for step 2 in % of IBase, if IN2> is greater than IN2>Max then IN2> is set to IN2>Max
ResetTypeCrv2 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step2 (Instantaneous / IEC / ANSI)
tReset2 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 2
tACrv2 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 2
tBCrv2 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 2
tCCrv2 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 2
tPRCrv2 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 2
tTRCrv2 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 2
tCRCrv2 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 2
IN3>Min 1 – 2500 %IB 1 1 Minimum used operate residual current level for step 3 in % of IBase, if IN3> is less than IN3>Min then IN3> is set to IN3>Min
IN3>Max 1 – 2500 %IB 1 2500 Maximum used operate residual current level for step 3 in % of IBase, if IN3> is greater than IN3>Max then IN3> is set to IN3>Max
ResetTypeCrv3 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step3 (Instantaneous / IEC / ANSI)
tReset3 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 3
tACrv3 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 3
tBCrv3 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 3
tCCrv3 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 3
tPRCrv3 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 3
tTRCrv3 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 3
tCRCrv3 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 3
IN4>Min 1 – 2500 %IB 1 1 Minimum used operate residual current level for step 4 in % of IBase, if IN4> is less than IN4>Min then IN4> is set to IN4>Min
IN4>Max 1 – 2500 %IB 1 2500 Maximum used operate residual current level for step 4 in % of IBase, if IN4> is greater than IN4>Max then IN4> is set to IN4>Max
ResetTypeCrv4 Instantaneous
IEC Reset
ANSI reset
Instantaneous Reset curve type for step4 (Instantaneous / IEC / ANSI)
tReset4 0.000 – 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 – 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 4
tACrv4 0.005 – 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 4
tBCrv4 0.00 – 20.00 0.01 0.00 Param B for customized inverse trip time curve for step 4
tCCrv4 0.1 – 10.0 0.1 1.0 Param C for customized inverse trip time curve for step 4
tPRCrv4 0.005 – 3.000 0.001 0.500 Param PR for customized inverse reset time curve for step 4
tTRCrv4 0.005 – 100.000 0.001 13.500 Param TR for customized inverse reset time curve for step 4
tCRCrv4 0.1 – 10.0 0.1 1.0 Param CR for customized inverse reset time curve for step 4

EF4PTOC Non group settings (basic)

EF4PTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups
SeqTypeIDir Zero seq
Neg seq
Zero seq Choice of measurand for directional current
SeqTypeIPol Zero seq
Neg seq
Zero seq Choice of measurand for polarizing current
SeqTypeUPol Zero seq
Neg seq
Zero seq Choice of measurand for polarizing voltage

EF4PTOC Monitored data

EF4PTOC Monitored data
Name Type Values (Range) Unit Description
IOp REAL A Operating current level
UPol REAL kV Polarizing voltage level
IPol REAL A Polarizing current level
UPOLIANG REAL deg Polarizing angle between voltage and current
IPOLIANG REAL deg Polarizing current angle

Logics & highlights


Logic for limitation of used operation current value

Logic for limitation of used operation current value

Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4

Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4

Operating characteristic for earth-fault directional element using the zero sequence components

Operating characteristic for earth-fault directional element using the zero sequence components

Simplified logic diagram for directional supervision element with integrated directional comparison step

Simplified logic diagram for directional supervision element with integrated directional comparison step

Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers feature

Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers feature

Simplified logic diagram for SOTF and under-time features

Simplified logic diagram for SOTF and under-time features

Functional overview of EF4PTOC

Functional overview of EF4PTOC

error: Content is protected !!