ABB / Instantaneous phase overcurrent protection (PHPIOC) _ Setting & highlights _ AB2034

Table of Contents

Overview

The “Instantaneous three phase overcurrent (PHPIOC)” function has a low transient overreach and short tripping time to allow use as a high set short-circuit protection function.

For more detailed information on “Instantaneous three phase overcurrent (PHPIOC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


PHPIOC Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous phase overcurrent protection PHPIOC 3I>> 50

Signals & Setting Parameters


PHPIOC function block

PHPIOC function block

PHPIOC Input signals

PHPIOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase current
BLOCK BOOLEAN 0 Block of function
ENMULT BOOLEAN 0 Enable current start value multiplier

PHPIOC Output signals

PHPIOC Output signals
Name Type Description
TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3

PHPIOC Group settings (basic)

PHPIOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OpMode 2 out of 3
1 out of 3
1 out of 3 Select operation mode 2-out of 3 / 1- out of 3
IP>> 5 – 2500 %IB 1 200 Operate phase current level in % of IBase

PHPIOC Group settings (advanced)

PHPIOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
IP>>Min 5 – 2500 %IB 1 5 Minimum used operate phase current level in % of IBase, if IP>> is less than IP>>Min then IP>> is set to IP>>Min
IP>>Max 5 – 2500 %IB 1 2500 Maximum used operate phase current level in % of IBase, if IP>> is greater than IP>>Max then IP>> is set to IP>>Max
StValMult 0.5 – 5.0 0.1 1.0 Multiplier for operate current level

PHPIOC Non group settings (basic)

PHPIOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

PHPIOC Monitored data

PHPIOC Monitored data
Name Type Values (Range) Unit Description
IL1 REAL A Current in phase L1
IL2 REAL A Current in phase L2
IL3 REAL A Current in phase L3

Logics & highlights


Logic for limitation of used operation current value

Logic for limitation of used operation current value