Overview

Sudden events in an electric power system such as large changes in load, fault occurrence or fault clearance, can cause power oscillations referred to as power swings. In a non-recoverable situation, the power swings become so severe that the synchronism is lost, a condition referred to as pole slipping. The main purpose of the “Pole slip protection (PSPPPAM)” is to
detect, evaluate, and take the required action for pole slipping occurrences in the power system.

For more detailed information on “Pole slip protection (PSPPPAM)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pole slip protection PSPPPAM Ucos 78

Signals & Setting Parameters


PSPPPAM function block

1-PSPPPAM function block

PSPPPAM Input signals

PSPPPAM Input signals
Name Type Default Description
I3P GROUP SIGNAL Current group connection
U3P GROUP SIGNAL Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOTOR BOOLEAN 0 Block operation in motor direction
EXTZONE1 BOOLEAN 0 Extension of zone1 with zone2 region

PSPPPAM Output signals

PSPPPAM Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip1 after the N1Limit slip in zone1
TRIP2 BOOLEAN Trip2 after the N2Limit slip in zone2
START BOOLEAN Common start signal
ZONE1 BOOLEAN First slip in zone1 region
ZONE2 BOOLEAN First slip in zone2 region
GEN BOOLEAN Generator is faster than the system
MOTOR BOOLEAN Generator is slower than the system
SFREQ REAL Slip frequency
SLIPZOHM REAL Slip impedance in ohms
SLIPZPER REAL Slip impedance in percent of ZBase
UCOS REAL UCosPhi voltage
UCOSPER REAL UCosPhi voltage in percent of UBase

PSPPPAM Group settings (basic)

PSPPPAM Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation On / Off
OperationZ1 Off
On
On Operation Zone1 On / Off
OperationZ2 Off
On
On Operation Zone2 On / Off
ImpedanceZA 0.00 – 1000.00 % 0.01 10.00 Forward impedance in % of Zbase
ImpedanceZB 0.00 – 1000.00 % 0.01 10.00 Reverse impedance in % of Zbase
ImpedanceZC 0.00 – 1000.00 % 0.01 10.00 Impedance of zone1 limit in % of Zbase
AnglePhi 72.00 – 90.00 Deg 0.01 85.00 Angle of the slip impedance line
StartAngle 0.0 – 180.0 Deg 0.1 110.0 Rotor angle for the start signal
TripAngle 0.0 – 180.0 Deg 0.1 90.0 Rotor angle for the trip1 and trip2 signals
N1Limit 1 – 20 1 1 Count limit for the trip1 signal
N2Limit 1 – 20 1 3 Count limit for the trip2 signal

PSPPPAM Group settings (advanced)

PSPPPAM Group settings (advanced)
Name Values (Range) Unit Step Default Description
ResetTime 0.000 – 60.000 s 0.001 5.000 Time without slip to reset all signals

PSPPPAM Non group settings (basic)

PSPPPAM Non group settings (basic)
Name Values (Range) Unit Step Default Description
MeasureMode PosSeq
L1L2
L2L3
L3L1
PosSeq Measuring mode (PosSeq, L1L2, L2L3, L3L1)
InvertCTcurr No
Yes
No Invert current direction
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

PSPPPAM Monitored data

PSPPPAM Monitored data
Name Type Values (Range) Unit Description
SFREQ REAL Hz Slip frequency
SLIPZOHM REAL Ohm Slip impedance in ohms
SLIPZPER REAL % Slip impedance in percent of ZBase
UCOS REAL kV UCosPhi voltage
UCOSPER REAL % UCosPhi voltage in percent of UBase

Logics & highlights


Movements in the impedance plain

2-Movements in the impedance plain

Different generator quantities as function of the angle between the equivalent generators

3-Different generator quantities as function of the angle between the equivalent generators

Simplified logic diagram for pole slip protection PSPPPAM

4-Simplified logic diagram for pole slip protection PSPPPAM