Overview

The “Power Swing Logic (PSLPSCH)” is a complementary function to Power Swing Detection (ZMRPSB) function. It provides possibility for selective tripping of faults on power lines during system oscillations (power swings or pole slips), when the distance protection function should normally be blocked.

For more detailed information on “Power Swing Logic (PSLPSCH)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Signals & Setting Parameters


PSLPSCH Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Power swing logic PSLPSCH

PSLPSCH function block

PSLPSCH function block

PSLPSCH Input signals

PSLPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
STZMUR BOOLEAN 0 Start of the underreaching zone
STZMOR BOOLEAN 0 Start of the overreaching zone
STPSD BOOLEAN 0 Power swing detected
STDEF BOOLEAN 0 Start from Earth Fault Protection in forward or reverse direction
STZMPSD BOOLEAN 0 Operation of Power Swing Detection external characteristic
CACC BOOLEAN 0 Overreaching ZM zone to be accelerated
AR1P1 BOOLEAN 0 Single pole auto-reclosing in progress
CSUR BOOLEAN 0 Carrier send by the underreaching power-swing zone
CR BOOLEAN 0 Carrier receive signal during power swing detection operation

PSLPSCH Output signals

PSLPSCH Output signals
Name Type Description
TRIP BOOLEAN Trip through Power Swing Logic
STZMURPS BOOLEAN Start of Underreaching zone controlled by PSL to be used in configuration
BLKZMUR BOOLEAN Block trip of underreaching impedance zone
BLKZMOR BOOLEAN Block trip of overreaching distance protection zones
CS BOOLEAN Carrier send signal controlled by the power swing

PSLPSCH Group settings (basic)

PSLPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
tDZ 0.000 – 60.000 s 0.001 0.050 Permitted max oper time diff between higher and lower zone
tDZMUR 0.000 – 60.000 s 0.001 0.200 Delay for oper of underreach zone with detected diff in oper time
tCS 0.000 – 60.000 s 0.001 0.100 Conditional timer for sending the CS at power swings
tTrip 0.000 – 60.000 s 0.001 0.100 Conditional timer for tripping at power swings
tBlkTr 0.000 – 60.000 s 0.001 0.300 Timer for blocking the overreaching zones trip

Logics & highlights


Simplified logic diagram – power swing communication and tripping logic

Simplified logic diagram – power swing communication and tripping logic

Control of underreaching distance protection (Zone 1) at power swings caused by the faults and their clearance on adjacent lines and other system elements

Control of underreaching distance protection (Zone 1) at power swings caused by the faults and their clearance on adjacent lines and other system elements