Overview

The “Automatic switch onto fault logic (ZCVPSOF)” is a function that gives an instantaneous trip when closing the breaker onto a fault. A dead-line detection check is provided to activate ZCVPSOF when the line is de-energized.

For more detailed information on “Automatic switch onto fault logic (ZCVPSOF)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


ZCVPSOF Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Automatic switch onto fault logic ZCVPSOF

Signals & Setting Parameters


ZCVPSOF function block

ZCVPSOF function block

ZCVPSOF Input signals

ZCVPSOF Input signals
Name Type Default Description
I3P GROUP SIGNAL Current DFT
U3P GROUP SIGNAL Voltage DFT
BLOCK BOOLEAN 0 Block of function
START_DLYD BOOLEAN 0 Start from function to be accelerated with delay by SOTF
BC BOOLEAN 0 External enabling of SOTF
ZACC BOOLEAN 0 Distance zone to be accelerated by SOTF

ZCVPSOF Output signals

ZCVPSOF Output signals
Name Type Description
TRIP BOOLEAN Trip output

ZCVPSOF Group settings (basic)

ZCVPSOF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
AutoInitMode DLD disabled
Voltage
Current
Current & Voltage
DLD disabled Automatic switch onto fault initialization
Mode Impedance
UILevel
UILvl&Imp
UILevel Mode of operation of SOTF Function
IPh< 1 – 100 %IB 1 20 Current level for detection of dead line in % of IBase
UPh< 1 – 100 %UB 1 70 Voltage level for detection of dead line in % of UBase
tDuration 0.000 – 60.000 s 0.001 0.020 Time delay for UI detection (s)
tSOTF 0.000 – 60.000 s 0.001 1.000 Drop off delay time of switch onto fault function
tDLD 0.000 – 60.000 s 0.001 0.200 Delay time for activation of dead line detection
tOperate 0.03 – 120.00 s 0.01 0.03 Time delay to operate of switch onto fault function

ZCVPSOF Non group settings (basic)

ZCVPSOF Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZCVPSOF Monitored data

ZCVPSOF Monitored data
Name Type Values (Range) Unit Description
IL1 REAL A Current in phase L1
IL2 REAL A Current in phase L2
IL3 REAL A Current in phase L3
UL1 REAL kV Voltage in phase L1
UL2 REAL kV Voltage in phase L2
UL3 REAL kV Voltage in phase L3

Logics & highlights


Simplified logic diagram for Automatic switch onto fault logic

Simplified logic diagram for Automatic switch onto fault logic