Overview

The “Power swing detection (ZMRPSB)” function is used to detect power swings and initiate block of all distance protection zones. Occurrence of earth-fault currents during a power swing inhibits the ZMRPSB function, to allow fault clearance.

For more detailed information on “Power swing detection (ZMRPSB)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


ZMRPSB Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Power swing detection ZMRPSB Zpsb 68

Signals & Setting Parameters


ZMRPSB function block

ZMRPSB function block

ZMRPSB Input signals

ZMRPSB Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKI01 BOOLEAN 0 Block inhibit of start output for slow swing condition
BLKI02 BOOLEAN 0 Block inhibit of start output for subsequent residual current detection
BLK1PH BOOLEAN 0 Block one-out-of-three-phase operating mode
REL1PH BOOLEAN 0 Release one-out-of-three-phase operating mode
BLK2PH BOOLEAN 0 Block two-out-of-three-phase operating mode
REL2PH BOOLEAN 0 Release two-out-of-three-phase operating mode
I0CHECK BOOLEAN 0 Residual current (3I0) detection used to inhibit start output
TRSP BOOLEAN 0 Single-pole tripping command issued by tripping function
EXTERNAL BOOLEAN 0 Input for external detection of power swing

ZMRPSB Output signals

ZMRPSB Output signals
Name Type Description
START BOOLEAN Power swing detected
ZOUT BOOLEAN Measured impedance within outer impedance boundary
ZIN BOOLEAN Measured impedance within inner impedance boundary

ZMRPSB Group settings (basic)

ZMRPSB Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Mode On / Off
X1InFw 0.01 – 3000.00 Ohm/p 0.01 30.00 Inner reactive boundary, forward
R1LIn 0.01 – 1000.00 Ohm/p 0.01 30.00 Line resistance for inner characteristic angle
R1FInFw 0.01 – 1000.00 Ohm/l 0.01 30.00 Fault resistance coverage to inner resistive line, forward
X1InRv 0.01 – 3000.00 Ohm/p 0.01 30.00 Inner reactive boundary, reverse
R1FInRv 0.01 – 1000.00 Ohm/l 0.01 30.00 Fault resistance line to inner resistive boundary, reverse
OperationLdCh Off
On
On Operation of load discrimination characteristic
RLdOutFw 0.01 – 3000.00 Ohm/p 0.01 30.00 Outer resistive load boundary, forward
ArgLd 5 – 70 Deg 1 25 Load angle determining load impedance area
RLdOutRv 0.01 – 3000.00 Ohm/p 0.01 30.00 Outer resistive load boundary, reverse
kLdRFw 0.50 – 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive load boundary, forward
kLdRRv 0.50 – 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive load boundary, reverse
tEF 0.000 – 60.000 s 0.001 3.000 Timer for overcoming single-pole reclosing dead time
IMinOpPE 5 – 30 %IB 1 10 Minimum operate current in % of IBase

ZMRPSB Group settings (advanced)

ZMRPSB Group settings (advanced)
Name Values (Range) Unit Step Default Description
tP1 0.000 – 60.000 s 0.001 0.045 Timer for detection of initial power swing
tP2 0.000 – 60.000 s 0.001 0.015 Timer for detection of subsequent power swings
tW 0.000 – 60.000 s 0.001 0.250 Waiting timer for activation of tP2 timer
tH 0.000 – 60.000 s 0.001 0.500 Timer for holding power swing START output
tR1 0.000 – 60.000 s 0.001 0.300 Timer giving delay to inhibit by the residual current
tR2 0.000 – 60.000 s 0.001 2.000 Timer giving delay to inhibit at very slow swing

ZMRPSB Non group settings (basic)

ZMRPSB Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Operating characteristic for ZMRPSB function (setting parameters in italic)

Operating characteristic for ZMRPSB function (setting parameters in italic)

Detection of power swing in phase L1

Detection of power swing in phase L1

Detection of power swing for 1-of-3 and 2-of-3 operating mode

Detection of power swing for 1-of-3 and 2-of-3 operating mode

Simplified block diagram for ZMRPSB function

Simplified block diagram for ZMRPSB function