ABB / Distance protection zone, quadrilateral characteristic, separate settings (ZMRPDIS, ZMRAPDIS and ZDRDIR) _ Setting & highlights _ AB2022

Table of Contents

Overview

The “Distance protection zone, quadrilateral characteristic (ZMRPDIS) together with Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS)” has functionality for load encroachment, which increases the possibility to detect high resistive faults on heavily loaded lines, as shown below:

1-Typical quadrilateral distance protection zone with Phase selection, quadrilateral characteristic with settable angle function FRPSPDIS activated

For more detailed information on this function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance protection zone, quadrilateral characteristic, separate settings (zone 1) ZMRPDIS Z< 21
Distance protection zone, quadrilateral characteristic, separate settings (zone 2-5) ZMRAPDIS Z< 21
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional impedance quadrilateral ZDRDIR Z<-> 21D

Signals & Setting Parameters


ZMRPDIS function block

2-ZMRPDIS function block

ZMRPDIS Input signals

ZMRPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMRPDIS Output signals

ZMRPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMRPDIS Group settings (basic)

ZMRPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
X1PP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph- Ph
R1PP 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-Ph
X1PE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph- E
R1PE 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-E
RFPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
X0PE 0.10 – 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
RFPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
R0PE 0.01 – 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic angle, Ph-E
OperationPP Off
On
On Operation mode Off / On of Phase- Phase loops
OpModetPP Off
On
On Operation mode Off / On of Zone timer, Ph-Ph
tPP 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
On Operation mode Off / On of Phase- Earth loops
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 – 1000 %IB 1 20 Minimum operate delta current for Phase-Phase loops
IMinOpPE 10 – 1000 %IB 1 20 Minimum operate phase current for Phase-Earth loops
IMinOpIN 5 – 1000 %IB 1 5 Minimum operate residual current for Phase-Earth loops

ZMRPDIS Non group settings (basic)

ZMRPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZMRAPDIS function block

3-ZMRAPDIS function block

ZMRAPDIS Input signals

ZMRAPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMRAPDIS Output signals

ZMRAPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMRAPDIS Group settings (basic)

ZMRAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
X1PP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph- Ph
R1PP 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-Ph
X1PE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach Ph- E
R1PE 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-E
RFPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
X0PE 0.10 – 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
RFPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
R0PE 0.01 – 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic angle, Ph-E
OperationPP Off
On
On Operation mode Off / On of Phase- Phase loops
OpModetPP Off
On
On Operation mode Off / On of Zone timer, Ph-Ph
tPP 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
On Operation mode Off / On of Phase- Earth loops
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 – 1000 %IB 1 20 Minimum operate delta current for Phase-Phase loops
IMinOpPE 10 – 1000 %IB 1 20 Minimum operate phase current for Phase-Earth loops

ZMRAPDIS Non group settings (basic)

ZMRAPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZDRDIR function block

4-ZDRDIR function block

ZDRDIR Input signals

ZDRDIR Input signals
Name Type Default Description
I3P GROUP SIGNAL group connection for current abs 2
U3P GROUP SIGNAL group connection for voltage abs 2

ZDRDIR Output signals

ZDRDIR Output signals
Name Type Description
STDIRCND INTEGER Binary coded directional information per measuring loop

ZDRDIR Group settings (basic)

ZDRDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
IMinOpPP 5 – 30 %IB 1 10 Minimum operate phase-phase current for Phase-Phase loops
IMinOpPE 5 – 30 %IB 1 5 Minimum operate phase current for Phase-Earth loops
ArgNegRes 90 – 175 Deg 1 115 Angle of blinder in second quadrant for forward direction
ArgDir 5 – 45 Deg 1 15 Angle of blinder in fourth quadrant for forward direction

ZDRDIR Non group settings (basic)

ZDRDIR Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


The different measuring loops at phase-to-earth fault and phase-to-phase fault

5-The different measuring loops at phase-to-earth fault and phase-to-phase fault

Characteristic for phase-to-earth measuring , ohm/loop domain

6-Characteristic for phase-to-earth measuring , ohm/loop domain

Characteristic for phase-to-phase measuring

7-Characteristic for phase-to-phase measuring

Fault loop model


Directional operating modes of the distance measuring zones

9-Directional operating modes of the distance measuring zones

Setting angles for discrimination of forward and reverse fault in Directional impedance quadrilateral function ZDRDIR

10-impedance quadrilateral function ZDRDIR

Conditioning by a group functional input signal STCND, external start condition

11- Conditioning by a group functional input signal STCND, external start condition

Composition of starting signals in non-directional operating mode

12-Composition of starting signals in non-directional operating mode

Composition of start signals in directional operating mode

13-Composition of start signals in directional operating mode

Tripping logic for the distance protection zone

14-Tripping logic for the distance protection zone