Overview

The “Mho impedance supervision logic (ZSMGAPC)” includes features for fault inception detection and high SIR detection. It also includes the functionality for loss of potential logic as well as for the pilot channel blocking scheme. ZSMGAPC can mainly be decomposed in two different parts: A fault inception detection logic, and High SIR detection logic.

For more detailed information on “Mho impedance supervision logic (ZSMGAPC)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Mho Impedance supervision logic ZSMGAPC

Signals & Setting Parameters


ZSMGAPC function block

Mho impedance supervision logic ZSMGAPC function block

ZSMGAPC Input signals

ZSMGAPC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase current samples and DFT magnitude
U3P GROUP SIGNAL Three phase phase-neutral voltage samples and DFT magnitude
BLOCK BOOLEAN 0 Block of the function
REVSTART BOOLEAN 0 Indication of reverse start
BLOCKCS BOOLEAN 0 Blocks the blocking carrier signal to remote end
CBOPEN BOOLEAN 0 Indicates that the breaker is open

ZSMGAPC Output signals

ZSMGAPC Output signals
Name Type Description
BLKZMTD BOOLEAN Block signal for blocking of time domained mho
BLKCHST BOOLEAN Blocking signal to remote end to block overreaching zone
CHSTOP BOOLEAN Stops the blocking signal to remote end
HSIR BOOLEAN Indication of source impedance ratio above set limit

ZSMGAPC Group settings (basic)

ZSMGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
PilotMode Off
On
Off Pilot mode Off/On
Zreach 0.1 – 3000.0 Ohm 0.1 38.0 Line impedance
IMinOp 10 – 30 %IB 1 20 Minimum operating current for SIR measurement

ZSMGAPC Group settings (advanced)

ZSMGAPC Group settings (advanced)
Name Values (Range) Unit Step Default Description
DeltaI 0 – 200 %IB 1 10 Current change level in % of IBase for fault inception detection
Delta3I0 0 – 200 %IB 1 10 Zero seq current change level in % of IBase
DeltaU 0 – 100 %UB 1 5 Voltage change level in % of UBase for fault inception detection
Delta3U0 0 – 100 %UB 1 5 Zero seq voltage change level in % of UBase
SIRLevel 5 – 15 1 10 Settable level for source impedance ratio

ZSMGAPC Non group settings (basic)

ZSMGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups