Overview

The “Full-scheme distance protection, quadrilateral for earth fault” functions have functionality for load encroachment, which increases the possibility to detect high resistive faults on heavily loaded lines

For more detailed information on “Full-scheme distance protection, quadrilateral for earth fault” functions, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fullscheme distance protection,quadrilateral for earth faults (zone 1) ZMMPDIS Z< 21
Fullscheme distance protection, quadrilateral for earth faults (zone 2-5) ZMMAPDIS Z< 21

Signals & Setting Parameters


ZMMPDIS function block

ZMMPDIS function block

ZMMPDIS Input signals

ZMMPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMMPDIS Output signals

ZMMPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMMPDIS Group settings (basic)

ZMMPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
X1 0.50 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.10 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone characteristic angle
X0 0.50 – 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 – 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic angle
RFPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 – 30 %IB 1 20 Minimum operate phase current for Phase-Earth loops
IMinOpIN 5 – 30 %IB 1 5 Minimum operate residual current for Phase-Earth loops

ZMMPDIS Non group settings (basic)

ZMMPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZMMAPDIS function block

ZMMAPDIS function block

ZMMAPDIS Input signals

ZMMAPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMMAPDIS Output signals

ZMMAPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMMAPDIS Group settings (basic)

ZMMAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
X1 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.10 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone characteristic angle
X0 0.50 – 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 – 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic angle
RFPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 – 30 %IB 1 20 Minimum operate phase current for Phase-Earth loops

ZMMAPDIS Non group settings (basic)

ZMMAPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


The different measuring loops at line-earth fault and phase-phase fault

The different measuring loops at line-earth fault and phase-phase fault

Characteristic for the phase-to-earth measuring loops, ohm/loop domain

Characteristic for the phase-to-earth measuring loops, ohm/loop domain

Fault loop model

Fault loop model

Directional operating modes of the distance measuring zone

Directional operating modes of the distance measuring zone

Setting angles for discrimination of forward and reverse fault

Setting angles for discrimination of forward and reverse fault

Conditioning by a group functional input signal STCND

Conditioning by a group functional input signal STCND

Composition of starting signals in non-directional operating mode

Composition of starting signals in non-directional operating mode

Composition of starting signals in directional operating mode

Composition of starting signals in directional operating mode

Tripping logic for the distance protection zone one

Tripping logic for the distance protection zone one