“Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)” function has functionality for load encroachment which increases the possibility to detect high resistive faults on heavily loaded lines.

1-Typical quadrilateral distance protection zone with load encroachment
function activated

For more detailed information on “Distance measuring zone, quadrilateral characteristic for series compensated lines (ZMCPDIS)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance measuring zone, quadrilateral characteristic for series compensated lines (zone 1) ZMCPDIS Z< 21
Distance measuring zone, quadrilateral characteristic for series compensated lines (zone 2-5) ZMCAPDIS Z< 21
Directional impedance quadrilateral, including series compensation ZDSRDIR Z<-> 21D

Signals & Setting Parameters


ZMCPDIS function block

2-ZMCPDIS function block

ZMCPDIS Input signals

ZMCPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMCPDIS Output signals

ZMCPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMCPDIS Group settings (basic)

ZMCPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
OperationPP Off
On
On Operation mode Off / On of Phase- Phase loops
X1FwPP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph, forward
R1PP 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-Ph
RFFwPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph, reverse
RFRvPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
OpModetPP Off
On
On Operation mode Off / On of Zone timer, Ph-Ph
tPP 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
On Operation mode Off / On of Phase- Earth loops
X1FwPE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-E, forward
R1PE 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-E
X0PE 0.10 – 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.01 – 3000.00 Ohm/p 0.01 47.00 Zero seq. resistance for zone characteristic angle, Ph-E
RFFwPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-E, reverse
RFRvPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 – 1000 %IB 1 20 Minimum operate delta current for Phase-Phase loops
IMinOpPE 10 – 1000 %IB 1 20 Minimum operate phase current for Phase-Earth loops
IMinOpIN 5 – 1000 %IB 1 5 Minimum operate residual current for Phase-Earth loops

ZMCPDIS Non group settings (basic)

ZMCPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZMCAPDIS function block

3-ZMCAPDIS function block

ZMCAPDIS Input signals

ZMCAPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

ZMCAPDIS Output signals

ZMCAPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or loop

ZMCAPDIS Group settings (basic)

ZMCAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationDir Non-directional
Forward
Reverse
Forward Operation mode of directionality NonDir / Forw / Rev
OperationPP Off
On
On Operation mode Off / On of Phase- Phase loops
X1FwPP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph, forward
R1PP 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-Ph
RFFwPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph, reverse
RFRvPP 0.10 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
OpModetPP Off
On
On Operation mode Off / On of Zone timer, Ph-Ph
tPP 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
On Operation mode Off / On of Phase- Earth loops
X1FwPE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-E, forward
R1PE 0.01 – 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for characteristic angle, Ph-E
X0PE 0.10 – 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.01 – 3000.00 Ohm/p 0.01 47.00 Zero seq. resistance for zone characteristic angle, Ph-E
RFFwPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.10 – 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-E, reverse
RFRvPE 0.10 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 – 1000 %IB 1 20 Minimum operate delta current for Phase-Phase loops
IMinOpPE 10 – 1000 %IB 1 20 Minimum operate phase current for Phase-Earth loops

ZMCAPDIS Non group settings (basic)

ZMCAPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZDSRDIR function block

4-ZDSRDIR function block

ZDSRDIR Input signals

ZDSRDIR Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input

ZDSRDIR Output signals

ZDSRDIR Output signals
Name Type Description
STFW BOOLEAN Start in forward direction
STRV BOOLEAN Start in reverse direction
STDIRCND INTEGER Binary coded directional information per measuring loop

ZDSRDIR Group settings (basic)

ZDSRDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
OperationSC NoSeriesComp
SeriesComp
SeriesComp Special directional criteria for voltage reversal
IMinOpPE 5 – 30 %IB 1 5 Minimum operate phase current for Phase-Earth loops
IMinOpPP 5 – 30 %IB 1 10 Minimum operate phase-phase current for Phase-Phase loops
ArgNegRes 90 – 175 Deg 1 130 Angle of blinder in second quadrant for forward direction
ArgDir 5 – 45 Deg 1 15 Angle of blinder in fourth quadrant for forward direction
INReleasePE 10 – 100 %IPh 1 20 3I0 limit for releasing phase-to-earth measuring loops
INBlockPP 10 – 100 %IPh 1 40 3I0 limit for blocking phase-to-phase measuring loops
OperationLdCh Off
On
On Operation of load discrimination characteristic
RLdFw 1.00 – 3000.00 Ohm/p 0.01 80.00 Forward resistive reach within the load impedance area
RLdRv 1.00 – 3000.00 Ohm/p 0.01 80.00 Reverse resistive reach within the load impedance area
ArgLd 5 – 70 Deg 1 30 Load angle determining the load impedance area
X1FwPP 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-Ph, forward
R1PP 0.10 – 1000.00 Ohm/p 0.01 7.00 Positive seq. resistance for characteristic angle, Ph-Ph
RFFwPP 0.50 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-Ph, reverse
RFRvPP 0.50 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
X1FwPE 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-E, forward
R1PE 0.10 – 1000.00 Ohm/p 0.01 7.00 Positive seq. resistance for characteristic angle, Ph-E
X0FwPE 0.50 – 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E, forward
R0PE 0.50 – 3000.00 Ohm/p 0.01 20.00 Zero seq. resistance for zone characteristic angle, Ph-E
RFFwPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-E, reverse
X0RvPE 0.50 – 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E, reverse
RFRvPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse

ZDSRDIR Non group settings (basic)

ZDSRDIR Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZDSRDIR Monitored data

ZDSRDIR Monitored data
Name Type Values (Range) Unit Description
L1Dir INTEGER 1=Forward
2=Reverse
0=No direction
Direction in phase L1
L2Dir INTEGER 1=Forward
2=Reverse
0=No direction
Direction in phase L2
L3Dir INTEGER 1=Forward
2=Reverse
0=No direction
Direction in phase L3
L1R REAL Ohm Resistance in phase L1
L1X REAL Ohm Reactance in phase L1
L2R REAL Ohm Resistance in phase L2
L2X REAL Ohm Reactance in phase L2
L3R REAL Ohm Resistance in phase L3
L3X REAL Ohm Reactance in phase L3

Logics & highlights


The different measuring loops at phase-to-earth fault and phase-to-phase fault

5-The different measuring loops at phase-to-earth fault and phase-to-phase

Characteristic for the phase-to-earth measuring loops, ohm/loop domain

6-Characteristic for the phase-to-earth measuring loops, ohm/loop domain

Characteristic for the phase-to-phase measuring loops

7-Characteristic for the phase-to-phase measuring loops

Fault loop model

8-Fault loop model

Directional operating modes of the distance measuring zone

9-Directional operating modes of the distance measuring zone

Setting angles for discrimination of forward and reverse fault

10-Setting angles for discrimination of forward and reverse fault

Conditioning by a group functional input signal STCND

11-Conditioning by a group functional input signal STCND

Composition of starting signals in non-directional operating mode

12-Composition of starting signals in non-directional operating mode

Composition of starting signals in directional operating mode

13-Composition of starting signals in directional operating mode

Tripping logic for the distance protection zone one

14-Tripping logic for the distance protection zone one