ABB / Phase selection, quad, fixed angle, load encroachment (FDPSPDIS) _ AB2015

Table of Contents

Phase selection with load encroachment, quadrilateral characteristic FDPSPDIS includes six impedance measuring loops; three intended for phase-to-earth faults, and three intended for phase-to-phase faults as well as for three-phase faults.

The difference, compared to the distance zone measuring function, is in the combination of the measuring quantities (currents and voltages) for different types of faults.

For more detailed information on “Phase selection, quad, fixed angle, load encroachment (FDPSPDIS)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase selection, quad, fixed angle, load encroachment FDPSPDIS Z<phs 21

FDPSPDIS function block

FDPSPDIS function block

FDPSPDIS Input signals

FDPSPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
DIRCND INTEGER 0 External directional condition

FDPSPDIS Output signals

FDPSPDIS Output signals
Name Type Description
TRIP BOOLEAN Trip output
START BOOLEAN Start in any phase or loop
STFWL1 BOOLEAN Fault detected in phase L1 – forward direction
STFWL2 BOOLEAN Fault detected in phase L2 – forward direction
STFWL3 BOOLEAN Fault detected in phase L3 – forward direction
STFWPE BOOLEAN Earth fault detected in forward direction
STRVL1 BOOLEAN Fault detected in phase L1 – reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 – reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 – reverse direction
STRVPE BOOLEAN Earth fault detected in reverse direction
STNDL1 BOOLEAN Non directional start in L1
STNDL2 BOOLEAN Non directional start in L2
STNDL3 BOOLEAN Non directional start in L3
STNDPE BOOLEAN Non directional start, phase-earth
STFW1PH BOOLEAN Start in forward direction for single-phase fault
STFW2PH BOOLEAN Start in forward direction for two- phase fault
STFW3PH BOOLEAN Start in forward direction for thre-phase fault
STPE BOOLEAN Current conditions release of phase-earth measuring elements
STPP BOOLEAN Current conditions release of phase-phase measuring elements
STCNDZ INTEGER Start condition (Z< with LE and 3I0 E/F detection)
STCNDLE INTEGER Start condition (only LE and 3I0 E/F detection)

FDPSPDIS Group settings (basic)

FDPSPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
INBlockPP 10 – 100 %IPh 1 40 3I0 limit for blocking phase-to-phase measuring loops
INReleasePE 10 – 100 %IPh 1 20 3I0 limit for releasing phase-to-earth measuring loops
RLdFw 1.00 – 3000.00 Ohm/p 0.01 80.00 Forward resistive reach within the load impedance area
RLdRv 1.00 – 3000.00 Ohm/p 0.01 80.00 Reverse resistive reach within the load impedance area
ArgLd 5 – 70 Deg 1 30 Load angle determining the load impedance area
X1 0.50 – 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
X0 0.50 – 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
RFFwPP 0.50 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
RFRvPP 0.50 – 3000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
RFFwPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
RFRvPE 1.00 – 9000.00 Ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
IMinOpPP 5 – 500 %IB 1 10 Minimum operate delta current for Phase-Phase loops
IMinOpPE 5 – 500 %IB 1 5 Minimum operate phase current for Phase-Earth loops

FDPSPDIS Group settings (advanced)

FDPSPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
OperationZ< Off
On
On Operation of impedance based measurement
OperationI> Off
On
Off Operation of current based measurement
IPh> 10 – 2500 %IB 1 120 Start value for phase over-current element
IN> 10 – 2500 %IB 1 20 Start value for trip from 3I0 over- current element
TimerPP Off
On
Off Operation mode Off / On of Zone timer, Ph-Ph
tPP 0.000 – 60.000 s 0.001 3.000 Time delay to trip, Ph-Ph
TimerPE Off
On
Off Operation mode Off / On of Zone timer, Ph-E
tPE 0.000 – 60.000 s 0.001 3.000 Time delay to trip, Ph-E

FDPSPDIS Non group settings (basic)

FDPSPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

highlights

Characteristics for non-directional, forward and reverse operation of Phase selection with load encroachment, quadrilateral characteristic FDPSPDIS

Characteristics for non-directional, forward and reverse operation of Phase selection with load encroachment, quadrilateral characteristic FDPSPDIS

Characteristic of FDPSPDIS for phase-to-earth fault (setting parameters in italic), ohm/loop domain (directional lines are drawn as “line-dot-dot-line”)

Characteristic of FDPSPDIS for phase-to-earth fault (setting parameters in italic), ohm/loop domain (directional lines are drawn as "line-dot-dot-line")

The operation characteristics for FDPSPDIS at phase-to-phase fault (setting parameters in italic, directional lines drawn as “line-dot-dot-line”), ohm/phase domain

The operation characteristics for FDPSPDIS at phase-to-phase fault (setting parameters in italic, directional lines drawn as "line-dot-dot-line"), ohm/phase domain

The characteristic of FDPSPDIS for three-phase fault (setting parameters in italic)

The characteristic of FDPSPDIS for three-phase fault (setting parameters in italic)

Characteristic of load encroachment function

Characteristic of load encroachment function

Difference in operating characteristic depending on operation mode when load encroachment is activated

Difference in operating characteristic depending on operation mode when load encroachment is activated

Operating characteristic in forward direction when load encroachment is activated

Operating characteristic in forward direction when load encroachment is activated

Operating characteristic for FDPSPDIS in forward direction for three-phase fault, ohm/phase domain

Operating characteristic for FDPSPDIS in forward direction for three-phase fault, ohm/phase domain

Rotation of load characteristic for a fault between two phases

Rotation of load characteristic for a fault between two phases

General phase-selection logic diagram

General phase-selection logic diagram

Phase-to-phase and phase-to-earth operating conditions (residual current criteria)

Phase-to-phase and phase-to-earth operating conditions (residual current criteria)

Composition on non-directional phase selection signals

Composition on non-directional phase selection signals

Composition of phase selection signals for reverse direction

Composition of phase selection signals for reverse direction

Composition of phase selection signals for forward direction

Composition of phase selection signals for forward direction

TRIP and START signal logic

TRIP and START signal logic