ABB / High impedance differential protection, single phase (HZPDIF) _ Setting & highlights _ AB2011

Table of Contents

Overview

The “High impedance differential protection, single phase (HZPDIF)” function can be used when the involved CT cores have the same turns ratio and similar magnetizing characteristics.

For more detailed information on “High impedance differential protection, single phase (HZPDIF)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here .


HZPDIF Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High impedance differential protection, single phase HZPDIF Id 87

Signals & Setting Parameters


HZPDIF Function block

HZPDIF Function block

HZPDIF Input signals

HZPDIF Input signals
Name Type Default Description
ISI GROUP SIGNAL Single phase current input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

HZPDIF Output signals

HZPDIF Output signals
Name Type Description
TRIP BOOLEAN Trip signal
ALARM BOOLEAN Alarm signal
MEASVOLT REAL Measured RMS voltage on CT secondary side

HZPDIF Group settings (basic)

HZPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
U>Alarm 5 – 500 V 1 10 Alarm voltage level in volts on CT secondary side
tAlarm 0.000 – 60.000 s 0.001 5.000 Time delay to activate alarm
U>Trip 10 – 900 V 1 100 Operate voltage level in volts on CT secondary side
SeriesResistor 50 – 20000 Ohm 1 250 Value of series resistor in Ohms

HZPDIF Monitored data

HZPDIF Monitored data
Name Type Values (Range) Unit Description
MEASVOLT REAL kV Measured RMS voltage on CT secondary side

Logics & highlights


HZPDIF scheme

HZPDIF scheme

Logic diagram for 1Ph High impedance differential protection HZPDIF

Logic diagram for 1Ph High impedance differential protection HZPDIF