ABB / 100% Stator earth fault protection, 3rd harmonic based (STEFPHIZ) _ Setting & highlights _ AB2139

Table of Contents

Overview

By the “100% Stator earth fault protection, 3rd harmonic based” either the 3rd harmonic voltage differential principle, the neutral point 3rd harmonic undervoltage principle or the terminal side 3rd harmonic overvoltage principle can be applied. However, differential principle is strongly recommended. Combination of these two measuring principles provides coverage for entire stator winding against earth faults.

For more detailed information on “100% Stator earth fault protection, 3rd harmonic based” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
100% Stator earth fault protection, 3rd harmonic based STEFPHIZ   59THD

Signals & Setting Parameters


STEFPHIZ function block

STEFPHIZ function block

STEFPHIZ Input signals

STEFPHIZ Input signals
Name Type Default Description
U3PNEUT GROUP SIGNAL Voltage connection neutral side
U3PTERM GROUP SIGNAL Open-Delta connection on Terminal side
BLOCK BOOLEAN 0 Complete block of the stator earth fault protecion function
BLOCK3RD BOOLEAN 0 Block of the 3rd harmonic-based parts of the protection
BLOCKUN BOOLEAN 0 Block of the fund. harmonic-based part of the protection
CBCLOSED BOOLEAN 1 TRUE means breaker between gen. & trafo is closed

STEFPHIZ Output signals

STEFPHIZ Output signals
Name Type Description
TRIP BOOLEAN Main, common trip command
TRIP3H BOOLEAN Trip by one of two 3rd harmonic voltage-based prot.
TRIPUN BOOLEAN Trip by fund. freq. neutral over-voltage protection
START BOOLEAN Main, common start signal
START3H BOOLEAN Start by one of two 3rd harmonic voltage-based prot.
STARTUN BOOLEAN Start signal by fund. freq. neutral over-voltage prot.
UT3 REAL Mag. of 3rd harm. voltage at generator terminal side, Volts
UN3 REAL Mag. of 3rd harm. voltage at generator neutral side, Volts
E3 REAL Total induced stator 3rd harmonic voltage, primary Volts
ANGLE REAL Angle between 3rd harmonic votage phasors, radians
DU3 REAL Diff. between 3rd harm. volt. at both sides of gen., Volts
BU3 REAL Bias voltage, a part of voltN3rdHarmonic, primary Volts
UN REAL Fund. frequency voltage at generator neutral, primary Volts

STEFPHIZ Group settings (basic)

STEFPHIZ Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
Beta 0.50 – 10.00 0.01 3.00 Portion of voltN3rdHarmonic used as bias
CBexists No Yes No Defines if generator CB exists (between Gen & Transformer)
FactorCBopen 1.00 – 10.00 0.01 1.00 Beta is multiplied by this factor when CB is open
UN3rdH< 0.5 – 10.0 %UB 0.1 2.0 Pickup 3rd Harm U< protection (when activated) % of UB/1,732
UT3BlkLevel 0.1 – 10.0 %UB 0.1 1.0 If UT3 is below limit 3rdH Diff is blocked, in % of UB/1,732
UNFund> 1.0 – 50.0 %UB 0.1 5.0 Pickup fundamental UN> protection (95% SEF), % of UB/1,732
t3rdH 0.020 – 60.000 s 0.001 1.000 Operation delay of 3rd harm-based protection (100% SEF) in s
tUNFund 0.020 – 60.000 s 0.001 0.500 Operation delay of fundamental UN> protection (95% SEF) in s

STEFPHIZ Non group settings (basic)

STEFPHIZ Non group settings (basic)
Name Values (Range) Unit Step Default Description
TVoltType NoVoltage
ResidualVoltage
AllThreePhases
PhaseL1
PhaseL2
PhaseL3
ResidualVoltage Used connection type for gen. terminal voltage transformer
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

STEFPHIZ Monitored data

STEFPHIZ Monitored data
Name Type Values (Range) Unit Description
UT3 REAL kV Mag. of 3rd harm. voltage at generator terminal side, Volts
UN3 REAL kV Mag. of 3rd harm. voltage at generator neutral side, Volts
E3 REAL kV Total induced stator 3rd harmonic voltage, primary Volts
ANGLE REAL deg Angle between 3rd harmonic votage phasors, radians
DU3 REAL kV Diff. between 3rd harm. volt. at both sides of gen., Volts
BU3 REAL kV Bias voltage, a part of voltN3rdHarmonic, primary Volts
UN REAL kV Fund. frequency voltage at generator neutral, primary Volts

Logics & highlights


Protection principles for STEFPHIZ function

Protection principles for STEFPHIZ function

Relation between the amplitude of the generator earth fault current and the fault time

Relation between the amplitude of the generator earth fault current and the fault time

Broken delta voltage transformer measurement of 3U0 voltage

Broken delta voltage transformer measurement of 3U0 voltage

Neutral point voltage transformer measurement of neutral point voltage (that is U0 voltage)

Neutral point voltage transformer measurement of neutral point voltage (that is U0 voltage)

Neutral point current measurement

Neutral point current measurement

Residual current measurement

Residual current measurement

Generator 3rd harmonic voltage characteristic at normal operation & protection algorithm

Generator 3rd harmonic voltage characteristic at normal operation & protection algorithm

Simplified logic diagram for stator earth fault protection

Simplified logic diagram for stator earth fault protection

Simplified Start and Trip logical diagram of the 100% Stator earth fault protection, 3rd harmonic based STEFPHIZ protection

Simplified Start and Trip logical diagram of the 100% Stator earth fault protection, 3rd harmonic based STEFPHIZ protection

Generator block with generator circuit breaker

Generator block with generator circuit breaker

Technical data

Technical data